HLF80K-D300-H2000 is a 80KW ultra-high efficiency DC/DC converter. Converts 1600-2000VDC to 120VDC with >97% efficiency. Designed with advanced liquid cooling, CAN communication & robust protection for extreme industrial and mobile applications.
Model HLF80K-D300-H2000
Power 80KW
Use To Drone
Input Voltage 1600-2000Vdc
Output Voltage 120Vdc
Size 400*300*200mm
Detail

HLF80K-D300-800

80kW Ultra-High Voltage DC/DC Converter for Data Centers


Overview

HLF80K-D300-800 is a high‑power, ultra‑high voltage DC/DC converter purpose‑built for modern data center power architectures. Delivering a continuous 80 kW from a 700–800 VDC input to a software‑configurable 300 VDC output at >97% peak efficiency,  serves as the high‑density power conversion core for HVDC distribution, renewable‑coupled microgrids, and next‑generation rack‑level power delivery. Engineered with liquid‑cooled thermal management, dual isolated CAN FD control, and a parallel‑ready architecture, this converter delivers the scalability, redundancy, and digital intelligence required for mission‑critical, high‑availability data center environments.


Key Features

FeatureDescription
80 kW Power DensityDelivers sustained full‑load output in a compact 500×400×200 mm form factor, reducing floor space and simplifying power system scaling.
Ultra‑High Voltage Input (700–800 VDC)Directly interfaces with 1500 VDC battery racks, photovoltaic strings, or high‑voltage DC microgrids, eliminating multiple conversion stages and improving overall system efficiency.
Software‑Configurable 300 VDC OutputFactory‑default 300 VDC; field‑programmable via CAN FD commands for future output variations, offering unmatched application versatility.
Advanced Digital Control & ProtectionDSP‑based adaptive algorithms ensure stable regulation under dynamic loads. Comprehensive protection suite includes UVP, OVP, OCP, SCP, OTP, with fault logging and predictive health monitoring.
Dual Isolated CAN FD InterfacesSeamlessly integrates with data center EMS, BMS, and SCADA for real‑time telemetry, remote configuration, and firmware updates.
Forced Liquid Cooling (Mandatory)Integrated cold plate with high‑capacity thermal management ensures reliable 80 kW operation even under continuous heavy loads, critical for 24/7 data center environments.
Redundancy‑Ready Parallel ArchitectureMaster‑less active current sharing supports up to 10 units in parallel (imbalance ≤±5%), enabling N+1, 2N, or scalable megawatt‑class power zones.

Applications in Data Centers

  • High‑Voltage DC (HVDC) Power Distribution – Converts 700–800 VDC from battery or rectifier sources to 300 VDC for feeding intermediate bus converters or direct server power shelves.

  • Renewable‑Powered Data Centers – Interfaces directly with large‑scale PV arrays or on‑site battery storage, enabling green, efficient DC‑coupled power delivery.

  • Colocation & Hyperscale Facilities – Serves as a modular, scalable power block for mega‑watt‑class DC power zones, reducing AC/DC conversion losses and copper costs.

  • Edge & Modular Data Centers – Compact size and robust cooling support rapid deployment in space‑constrained environments.

  • Backup & UPS Integration – Provides a stable DC bus for lithium‑ion battery systems, ensuring seamless transition to stored energy during grid outages.

  • High‑Availability Rack Power – Directly powers 300 VDC input servers or feeds intermediate bus converters for 48 V or 12 V rack distribution.


Technical Specifications

ParameterSpecification
ModelHLF80K-D300-800
Input Voltage Range700 – 800 VDC
Output Voltage300 VDC (factory‑default; field‑programmable via CAN)
Output Power80 kW continuous
Output Current (nominal)~267 A @ 300 VDC
Peak Efficiency> 97% @ 50–100% load; > 96.5% @ full load
Thermal Dissipation~2.8 kW @ full load (coolant inlet ≤45°C, flow ≥10 L/min)
Standby Power Consumption< 15 W (idle mode)
Communication & ControlDual isolated CAN FD 2.0 (with CAN‑open protocol support), full digital monitoring, data logging, and firmware over‑the‑air (FOTA) capability
ProtectionsUnder‑voltage (UVP), over‑voltage (OVP), over‑current (OCP), short‑circuit (SCP), over‑temperature (OTP), reverse polarity, input surge
Fault DiagnosticsReal‑time fault logging with time‑stamped event history; predictive health monitoring via AI‑ready telemetry
Parallel OperationActive current sharing with ±5% imbalance (master‑less architecture), supports up to 10 units in parallel
Cooling SystemForced liquid cooling (mandatory); cold plate integrated; recommended coolant: water‑glycol mixture (30%–50% glycol)
Coolant Flow Rate≥ 10 L/min (recommended); 8 L/min (minimum for derated operation)
Coolant Inlet Temperature-20°C to +55°C (full power up to 45°C; derating above 45°C)
Dimensions (L × W × H)400 × 300 × 200 mm (19.7 × 15.7 × 7.9 in)
Weight≤ 25 kg (55.1 lbs)
Operating Temperature-40°C to +85°C (ambient, with derating above 55°C)
Storage Temperature-40°C to +85°C
Relative Humidity5% – 95% (non‑condensing)
Altitude≤ 3000 m (derating above 2000 m)
MTBF> 500,000 hours (Telcordia SR‑332, ground fixed, 40°C)
MTTR< 30 minutes (field‑replaceable modules)
Safety & ComplianceCompliant with IEC 61800‑5‑1; architecture aligned with ISO 26262 ASIL‑D functional safety concepts

Protection & Safety Features

Protection TypeDescription
Input Under‑Voltage Lockout (UVLO)Shuts down when input drops below 650 VDC; auto‑restart upon recovery
Input Over‑Voltage Protection (OVP)Shuts down when input exceeds 850 VDC; auto‑restart upon recovery
Output Over‑Voltage ProtectionClamps output at 320 VDC; latches off for fault, requires reset
Output Over‑Current ProtectionLimits current at 295 A (110% of nominal); constant current mode with foldback after 10 seconds
Short‑Circuit ProtectionHiccup mode with auto‑recovery; protects against sustained output short
Over‑Temperature ProtectionShuts down at 90°C (coolant outlet); auto‑restart when temperature drops to 75°C
Reverse Polarity ProtectionInput protected against reverse connection (≤ -100 VDC for 1 minute)
Input Surge ProtectionWithstands 1000 VDC surges for 100 ms per IEC 61000‑4‑5

Why Choose the HLF80K-D300-800?

✅ Proven Efficiency for Hyperscale
Delivers > 97% peak efficiency, directly improving Power Usage Effectiveness (PUE) and reducing annual energy costs by thousands of dollars per megawatt.

✅ True Redundancy with Active Current Sharing
Parallel up to 10 units with < 5% current imbalance, enabling N+1, 2N, or distributed redundancy architectures without external controllers.

✅ Certified for Mission‑Critical Uptime
Fully compliant with IEC 61800‑5‑1, with hardware designed to support ISO 26262 ASIL‑D functional safety, ensuring 99.999% availability in demanding data center environments.

✅ Intelligent, Software‑Defined Power Core
Enables remote configuration, firmware updates, predictive maintenance alerts, and energy optimization algorithms via CAN FD.

✅ Thermally Optimized for Continuous Heavy Loads
Liquid‑cooled cold plate with optimized thermal resistance ensures stable operation under 80 kW continuous load.

✅ Built for Extreme Conditions
Rugged industrial design rated from -40°C to +85°C, with comprehensive surge and transient protection, ensures reliable 24/7/365 operation.

✅ Scalable Building Block for Megawatt Systems
Modular design allows scaling from 80 kW to 8 MW+ by paralleling multiple units.


Ordering & Support

HLF80K-D300-800 is engineered for the most demanding data center power challenges.

Custom output voltage configurations and extended temperature ranges are available upon request.

For detailed technical specifications, thermal integration guidelines, parallel configuration support, or to discuss your specific application requirements, please contact our Data Center Power Solutions Engineering Team.


This document is for informational purposes and may be updated without notice. All specifications are subject to change. For the latest version, please contact the manufacturer.